Golcar Passivhaus: Ground Floor & Foundations

The ground floor detailing at the project is very similar to that at the Denby Dale Passivhaus, with a few notable tweaks….


Ground floor detailing – exploring alternative approaches

We did look into using a floating / completely thermal bridge free ground floor/ wall junction. This would have involved building the concrete blockwork inner leaf and ground floor slab off the underfloor insulation and not needing to take the insulation in the cavity down to the foundation strip.
However, the loading on the inner leaf (which additionally carries the intermediate floor and roof) would have been so great that we would have had to upgrade the insulation in terms of compressive strength. This would have a) put the price up and b) lowered the lamda/ U value of the underfloor insulation.

So adding it all together it made sense to go  back to the original Denby Dale groundfloor detailing. We did, however, make a few key changes/ improvements to the original detailing:

Damp proof membrane

As at Denby Dale, we’re using the Celcon low thermal conductivity blocks again in the inner leaf below the groundfloor slab to reduce the path of the thermal bridge down to the strip foundations. But this time, learning lessons from Steel Farm (Mark Siddall from LEAP Architecture’s cavity wall Passivhaus project) we have taken the damp proof membrane around the first course of Celcon block below the groundfloor slab, which means it will stay dry and maintain its lamda value. We’ve then dressed the damp proof membrane up within the cavity and back into the inner DPC. At Denby Dale we don’t think it is a real problem, as it was a very dry site, but this is a ‘belt and braces’ approach that Mark Siddall introduced us to.

Polystyrene insulation – change in specification

We have also changed the type of polystyrene we’re using in the cavity, below the cavity tray down to the foundation strip. We have discovered that extruded polystyrene is more water repellent than the expanded polystyrene we used at Denby Dale. So, for the Golcar Passivhaus we’ve decided to use Knauf Polyfoam extruded polystyrene to minimise the risk of moisture affecting the thermal performance of insulation.

Underfloor insulation– change in specification

For the underfloor insulation in the slab itself, we’ve used 200mm polyurethane under the slab because of its better lamda values. (0.022).

The next blog will look at window & door thresholds and positioning within the insulation to minimise thermal bridging..

Bill Butcher, Director, Green Building Store www.greenbuildingstore.co.uk










Change the way you think about energy